| Brand Name |
JHR |
| Place of Origin |
Hebei China (Mainland) |
| Model Number |
GFNDP |
FRP Square Couter Flow Cooling Tower 1.Material of cooling tower could bear -50 degrees. 2.Turbidity degree of circular water is not more than 50mg/l, short time, it's not more than 100 mg/l. It shouldn't contain oil stain and mechanical impurity. 3.Direction of intake and output pipe could be turned according to 90 degree, 180 degree and 270 degree. 4.Water distribution system is designed in accordance with nominal water quantity 5.Blade installation degree of fans is adjustable, but need to ensure the same angle, and electric current of motor can't be above the rated current. 6.Fans could turn oppositely at low speed in a short time, in order to deice. 7.When the water pond of cooling tower is used as water pool, it need install another " automatically supplying water pipe" "rapidly supplying water pipe" "draining pipe" "warning pipe", this should be specially indicated when ordering, our quotation of cooling tower doesn't contain this part. 8.It also should be indicated if you require cooling tower retardant flame. SPECIFICATION Type Specification Coolingquantity Fansairflow (m3 /h) motor Waterpressureofinput (Kpa) Deadweight (t) Deadweight (t) NoisedB(A) t=28°C t=27°C Power (KW) Quantity (sets) Standardnormaltype FBL-50 50 57 36 1.5 1 23 0.6 1.43 65 FBL-75 75 85 50 3 1 25 1.3 2.09 66 FBL-100 100 114 65 4 1 30 1.5 2.35 66 FBL-150 150 170 90 5.5 1 55 2.1 3.68 67 FBL-200 200 228 138 7.5 1 58 3.3 5.41 68 FBL-300 300 342 200 7.5 1 60 4.7 7.87 69 FBL-400 400 456 240 11 1 65 7.2 11.4 70 FBL-500 500 170 320 15 1 75 8.1 12 72 FBL-600 600 687 400 22 1 80 10.2 16.53 74 FBL-750 750 856 480 30 1 90 12.5